CageLab
Free planning tool

Rack and Power Requirements Builder

Calculate your total IT load, rack count, recommended power configuration and space requirements before approaching operators. Enter your inputs and get a deployment summary.

Your deployment

Standard 1U servers: 200 to 400 W. GPU servers: 1,000 to 5,000 W.

Standard air cooling: under 20 kW. Enhanced air (in-row): 2040 kW. Liquid cooling: above 40 kW.

Deployment summary

12.0 kW

Total IT load

13.8 kW

Design load (with redundancy)

2 racks

Rack count

3 m²

Est. gross floor area

Floor area includes hot and cold aisles (600 mm × 1,200 mm cabinet, ~2× gross multiplier — planning estimate). Net cabinet area only: 1.4 m².

Power specification

Suggested power feed75 A × 2 feeds (A+B)
Design load13.8 kW
RedundancyN+1

Power feed sized at 80% of breaker rating — standard electrical design practice (IET Wiring Regulations). This is a planning convention, not a statutory requirement.

Recommended configuration

Dual UPS (N+1), dual A+B power feeds per rack. Each feed sized for full load.

Talk to Cagelab about your deployment

How to use these figures

The outputs from this tool give you a specification to take to colocation providers when requesting quotes. When approaching operators, you should specify your total IT load in kW, your rack density requirement in kW per rack, your redundancy requirement, and your target power feed specification.

Most operators will require a minimum commitment period and will quote based on your power draw, rack count and specific requirements. Having these figures ready before initial contact shortens the sales cycle considerably and signals to the operator that you know what you need.

If your density exceeds 20 kW per rack, use the AI Readiness and GPU Colocation Checker to assess whether you need facilities with enhanced cooling capability.

Need help interpreting your results? Get in touch.